Vol 1 , Issue 2 , April - June 2013 | Pages: 79-91 | Research Paper
Received: August 05, 2013 | Revised: August 22, 2013 | Accepted: August 28, 2013 | Published Online: September 20, 2013
Author Details
( * ) denotes Corresponding author
The methods for improving first law and second law efficiency have been considered in this paper. Detailed energy and exergy analysis of multi-evaporators at different temperatures with multiple compressors and multiple expansion valves in parallel and series with intercooler and flash chambers in the six type vapour compression refrigeration systems for finding irreversibilities in the systems have been done in terms of performance parameter for eco-friendly R134a, R290, R600, R600a, R1234yf, R1234ze, R404a and R152a and conventional R12, R502refrigerants. The numerical computations have been carried out for six systems. It was observed that first law and second law efficiency improved by 22%. It was also observed that performance of above six systems using R600 and R152a nearly matching same values under the accuracy of 5% can be used in the above system .But difficulties using R600, R290 and R600a have flammable problems therefore safety measures are required using these refrigerants, therefore R134a refrigerant is recommended for practical and commercial applications although it has slightly less thermal performance than R152a which is not widely used refrigerant for domestic and industrial applications.
Keywords
Vapour Compression Refrigeration Systems First and second Law Analysis, Irreversibility Analysis in VCR